GENERAL
Maximum Pressure............Refer to Pressure Range Table
Media Compativility.........Air and Liquid gases
Pressure Range..............0 to 5000PSI or Equivalent
ELECTRICAL
Power Supply................220VAC 50 ~ 60Hz(opt. 110VAC)
Relay Contact...............Screw terminal block
Display.....................4 digit LED
Warm-up Time................10 minutes
ELECTRICAL(Switches)
Power Supply................110 / 250VAC 50 ~ 60Hz
Relay Contact...............2 SPDT (NC - COM - NO)
Contact Rating..............10A @ 110VAC, 6A @ 250VAC
Connection..................6 screw terminal block
Level Setting...............Adjustable HIGH & LOW level
ELECTRICAL(Transmitter) (SIT only)
Connections.................2 screw terminal block
Output Siganl...............4-20 mA DC limited at 30mA DC
Loop Resistance............0-1100 ohms
Zero and Span Adjustment....Panel Adjustable
PERFORMANCE AT 23¡É
Zero Output.................4 mA
Full Span Output............20 mA
Accuracy..................¡¾0.25% FS (Includes Linearity,
Hysteresis & Repeatability)
Operating Temperature.......-10¡É ~ +70¡É
MECHANICAL
Pressure Connections........1/8", 1/4", 3/8", 1/2 PT male
Materials...................Aluminum Case, Connection S316 |